Dependency: See also: p0310, p1959
See also: F07984, F07985
Note
In order to calculate the inertia, sudden speed changes are carried out - the specified value corresponds to the lower
speed setpoint. This value is increased by 20 % for the upper speed value.
The q leakage inductance (refer to p1959.5) is determined at zero speed and at 50 % of p1965 - however, with a
maximum output frequency of 15 Hz and at a minimum of 10% of the rated motor speed.
p1967 Speed_ctrl_opt dynamic factor / n_opt dyn_factor
Access level: 3 Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
1 [%]
Max:
400 [%]
Factory setting:
100 [%]
Description: Sets the dynamic response factor for speed controller optimization.
After optimization, the dynamic response achieved is displayed in r1968.
Dependency: See also: p1959, r1968
See also: F07985
Note
For a rotating measurement, this parameter can be used to optimize the speed controller.
p1967 = 100 % --> speed controller optimization according to a symmetric optimum.
p1967 > 100 % --> optimization with a higher dynamic response (Kp higher, Tn lower).
If the actual dynamic response (see r1968) is significantly reduced with respect to the required dynamic response
(p1967), then this can be as a result of mechanical load oscillations. If, in spite of this load behavior, a higher dynamic
response is required, then the oscillation test (p1959.4 = 0) should be deactivated and the measurement repeated.
r1968 Speed_ctrl_opt dynamic factor actual / n_opt dyn_fact act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Displays the dynamic factor which is actually achieved for the vibration test
Dependency: See also: p1959, p1967
See also: F07985
Note
This dynamic factor only refers to the control mode of the speed controller set in p1960.
r1969 Speed_ctrl_opt moment of inertia determined / n_opt M_inert det
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: 25_1 Unit selection: p0100 Function diagram: -
Min:
- [kgm²]
Max:
- [kgm²]
Factory setting:
- [kgm²]
Description: Displays the determined moment of inertia of the drive.
After it has been determined, the value is transferred to p0341, p0342.
Dependency: IEC drives (p0100 = 0): unit kg m^2
NEMA drives (p0100 = 1): unit lb ft^2
See also: p0341, p0342, p1959
See also: F07984
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 729