Description: Display and connector output for the upper torque limit of all torque limits without offset.
Dependency: See also: p1520, p1521, p1522, p1523, p1528, p1529
r1527 CO: Torque limit lower without offset / M_max low w/o offs
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dynamic index: -
Unit group: 7_1 Unit selection: p0505 Function diagram: 6060, 6630,
6640
Min:
- [Nm]
Max:
- [Nm]
Factory setting:
- [Nm]
Description: Display and connector output for the lower torque limit of all torque limits without offset.
Dependency: See also: p1520, p1521, p1522, p1523, p1528, p1529
p1528[0...n] CI: Torque limit upper scaling / M_max upper scal
Access level: 4 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: PERCENT Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 6630
Min:
-
Max:
-
Factory setting:
1524[0]
Description: Sets the signal source for the scaling of the upper torque limit in p1522.
DANGER
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Negative values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1529[0...n] CI: Torque limit lower scaling / M_max lower scal
Access level: 4 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: PERCENT Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 6630
Min:
-
Max:
-
Factory setting:
1525[0]
Description: Sets the signal source for the scaling of the lower torque limit in p1523.
DANGER
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.