p0369[0...n] Motor saturation characteristic I_mag 4 / Mot sat. I_mag 4
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: 6723, 6838
Min:
5.0 [%]
Max:
800.0 [%]
Factory setting:
210.0 [%]
Description: The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the x coordinate (magnetizing current) for the 4th value pair of the characteristic.
Sets the fourth magnetization current of the saturation characteristic in [%] with reference to the rated magnetization
current (r0331).
Dependency: The following applies for the magnetizing currents:
p0366 < p0367 < p0368 < p0369
See also: p0365
Note
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
r0370[0...n] Motor stator resistance cold / Mot R_stator cold
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: -
Min:
- [ohm]
Max:
- [ohm]
Factory setting:
- [ohm]
Description: Displays the motor stator resistance at an ambient temperature (p0625).
The value does not include the cable resistance.
Dependency: See also: p0625
r0372[0...n] Cable resistance / Mot R_cable
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: -
Min:
- [ohm]
Max:
- [ohm]
Factory setting:
- [ohm]
Description: Displays the total cable resistance between power unit and motor, as well as the internal converter resistance.
Dependency: See also: r0238, p0352
r0373[0...n] Motor rated stator resistance / Mot R_stator rated
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: -
Min:
- [ohm]
Max:
- [ohm]
Factory setting:
- [ohm]
Description: Displays the rated motor stator resistance at rated temperature (total of p0625 and p0627).
Dependency: See also: p0627
Note
The parameter is not used for synchronous motors (p0300 = 2xx).