4.1.4.5 Connecting the cable shields (FSA ... FSG only)
For EMC-compliant wiring, you must connect the cable shields to the shield plate of the
converter.
Use shielded cables for the following connection:
Communication cable
Control cable
Motor cable
Before connecting the cable shields, you need to strip the cable insulation.
The following illustrations take converters with PROFINET interfaces as examples.
Connecting the cable shields, FSA ... FSC converters
The shield support for converter FSB is displayed as
an example.
Unshielded line cable
Cable tie
Unshielded communication cable
Unlacquered, good electrically conducting
mounting plate
Shielded control cable
Toothed tape
Shielded motor cable
Wiring
4.1 Line supply and motor
SINAMICS G120X converter
96 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC