Parameter
Number Name Factory setting
r0046.0…31 CO/BO: Missing enable signals -
p0857 Power unit monitoring time 10000 ms
p0858[C] BI: Unconditionally close holding brake 0
p0860 BI: Line contactor feedback signal 863.1
p0861 Line contactor monitoring time 100 ms
p1226[D] Speed threshold for standstill detection 20 rpm
p1227 Standstill detection monitoring time 300 s
p1228 Pulse suppression delay time 0.01 s
For additional information on parameters, please refer to the parameter list.
6.3.2 Adapt the default setting of the terminal strips
Overview
In the converter, the input and output signals are interconnected with specific converter
functions using special parameters. The following parameters are available to interconnect
signals:
● Binectors BI and BO are parameters to interconnect binary signals.
● Connectors CI and CO are parameters to interconnect analog signals.
The following chapters describe how you adapt the function of individual converter inputs and
outputs using binectors and connectors.
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
186 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC