EasyManua.ls Logo

Siemens SINAMICS G120X - Comm if Address; Comm Add; Comm if Baud Rate; Comm Baud; Reference Temperature; Ref Temp

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Note
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
The reference power is calculated as follows:
- 2 * Pi * reference speed / 60 * reference torque (motor)
- reference voltage * reference current * root(3) (infeed)
p2006 Reference temperature / Ref temp
Access level: 3 Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: -
Unit group: 21_1 Unit selection: p0505 Function diagram: -
Min:
50.00 [°C]
Max:
300.00 [°C]
Factory setting:
100.00 [°C]
Description: Sets the reference quantity for temperature.
All temperatures specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
p2010 Comm IF baud rate / Comm baud
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
6
Max:
12
Factory setting:
12
Description: Sets the baud rate for the commissioning interface (USS, RS232).
Value: 6: 9600 baud
7: 19200 baud
8: 38400 baud
9: 57600 baud
10: 76800 baud
11: 93750 baud
12: 115200 baud
Note
COMM-IF: Commissioning interface
The parameter is not influenced by setting the factory setting.
p2011 Comm IF address / Comm add
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
31
Factory setting:
2
Description: Sets the address for the commissioning interface (USS, RS232).
Note
The parameter is not influenced by setting the factory setting.
Parameters
7.2 Parameter list
SINAMICS G120X converter
734 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC