Dependency: See also: p0840, p1058
NOTICE
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1056[0...n] BI: Jog bit 1 / Jog bit 1
G120X_DP,
G120X_PN
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2501, 3030
Min:
-
Max:
-
Factory setting:
[0] 0
[1] 722.1
[2] 0
[3] 0
Description: Sets the signal source for jog 2.
Recommendation: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency: See also: p0840, p1059
NOTICE
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1056[0...n] BI: Jog bit 1 / Jog bit 1
G120X_USS Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2501, 3030
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for jog 2.
Recommendation: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency: See also: p0840, p1059
NOTICE
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1058[0...n] Jog 1 speed setpoint / Jog 1 n_set
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3001, 3030
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
150.000 [rpm]
Description: Sets the speed for jog 1.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency: See also: p1055, p1056