Index: [0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Note
AO: Analog Output
X202: IO module terminal
r0785.0...2 BO: CU analog outputs status word / CU AO ZSW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status of analog outputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 AO 0 negative Yes No -
01 AO 1 negative Yes No -
02 AO 2 negative Yes No -
Note
AO: Analog Output
p0791[0...2] CO: Fieldbus analog outputs / Fieldbus AO
G120X_USS Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-200.000 [%]
Max:
200.000 [%]
Factory setting:
0.000 [%]
Description: Setting and connector output to control the analog outputs via fieldbus.
Index: [0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Dependency: See also: p0771
Note
AO: Analog Output
The following interconnections must be established to control the analog outputs via fieldbus:
- AO 0: p0771[0] with p0791[0]
- AO 1: p0771[1] with p0791[1]
- AO 2: p0771[2] with p0791[2]
X202: IO module terminal
p0795 CU digital inputs simulation mode / CU DI simulation
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2201, 2221,
2256
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0000 bin
Description: Sets the simulation mode for digital inputs.
Bit field: Bit Signal name 1 signal 0 signal FP
Parameters
7.2 Parameter list
SINAMICS G120X converter