8.1.5 Message for a memory card that is not inserted
Function description
The converter identifies that a memory card is not inserted, and signals this state. The message
is deactivated in the converter factory setting.
Activate message
Procedure
1. Set p2118[x] = 1101, x = 0, 1, … 19
2. Set p2119[x] = 2
Message A01101 for a memory card that is not inserted is activated.
To cyclically signal to the higher-level control that a memory card is not inserted, connect
parameter r9401 to the send data of the fieldbus interface.
Deactivate message
Procedure
1. Set p2118[x] = 1101, x = 0, 1, … 19
2. Set p2119[x] = 3
Message A01101 for a memory card that is not inserted is deactivated.
Parameter
Parameter Explanation Factory setting
p2118[0 … 19] Change message type, message number 0
p2119[0 … 19] Change message type, type 0
r9401 Safely remove memory card status -
Saving the settings and series commissioning
8.1 Memory card
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 945