p4095 PM330 digital inputs simulation mode / PM330 DI sim_mode
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description: Sets the simulation mode for digital inputs of the PM330 power unit.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.3, external alarm) Simulation Terminal eval -
01 DI 1 (X9.4, external fault) Simulation Terminal eval -
02 DI 2 (X9.5, Emergency Off category 0) Simulation Terminal eval -
03 DI 3 (X9.6, Emergency Off category 1) Simulation Terminal eval -
Dependency: The setpoint for the input signals is specified using p4096.
See also: p4096
Note
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
p4096 PM330 digital inputs simulation mode setpoint / PM330 DI sim setp
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2275
Min:
-
Max:
-
Factory setting:
0000 bin
Description: Sets the setpoint for the input signals in the digital input simulation mode of the PM330 power unit.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.3, external alarm) High Low -
01 DI 1 (X9.4, external fault) High Low -
02 DI 2 (X9.5, Emergency Off category 0) High Low -
03 DI 3 (X9.6, Emergency Off category 1) High Low -
Dependency: The simulation of a digital input is selected using p4095.
See also: p4095
Note
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
p5350[0...n] Mot_temp_mod 1/3 boost factor at standstill / Standst boost_fact
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: 8017
Min:
1.0000
Max:
2.0000
Factory setting:
2.0000
Parameters
7.2 Parameter list
SINAMICS G120X converter
854 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC