r4022.0...3 CO/BO: PM330 digital inputs status / PM330 DI status
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status of the digital inputs of the PM330 power unit.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.3, external alarm) High Low -
01 DI 1 (X9.4, external fault) High Low -
02 DI 2 (X9.5, Emergency Off category 0) High Low -
03 DI 3 (X9.6, Emergency Off category 1) High Low -
Dependency: See also: r4023
Note
DI: Digital Input
r4023.0...3 CO/BO: PM330 digital inputs status inverted / PM330 DI stat inv
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the inverted status of the digital inputs of Power Module 330 (PM330).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.3, external alarm) High Low -
01 DI 1 (X9.4, external fault) High Low -
02 DI 2 (X9.5, Emergency Off category 0) High Low -
03 DI 3 (X9.6, Emergency Off category 1) High Low -
Dependency: See also: r4022
Note
DI: Digital Input
r4047 PM330 digital outputs status / PM330 DO status
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status of the digital outputs of Power Module 330 (PM330).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (X9.8: enable signal UDC link charged) High Low -
01 DO 1 (X9.11/X9.12: main contactor control) High Low -
Note
DO: Digital Output
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 853