Description: Display and connector output for the energy values at the output terminals of the power unit.
Index: [0] = Energy balance (sum)
[1] = Energy drawn
[2] = Energy fed back
Dependency: See also: p0043
Note
The signal can be displayed as process variable (scaling: 1 = 1 Wh).
This is enabled in p0043.
The display is also reset with p0040 = 1.
If an enable is present in r0043 when the Control Unit powers up, then the value from r0039 is transferred into r0042.
As r0039 serves as a reference signal for r0042, due to format reasons, the process energy display can only process
values of r0039 up to 2147483 kWh. r0039 should also be reset using this value.
p0043 BI: Enable energy usage display / Enab energy usage
Access level: 2 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to enable/reset the process energy display in r0042.
BI: p0043 = 1 signal:
The process energy display is enabled in r0042.
Dependency: See also: r0042
p0045 Display values smoothing time constant / Disp_val T_smooth
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 6799
Min:
0.00 [ms]
Max:
10000.00 [ms]
Factory setting:
4.00 [ms]
Description: Sets the smoothing time constant for the following display values:
r0063[1], r0068[1], r0080[1], r0082[1].
r0046.0...31 CO/BO: Missing enable signal / Missing enable sig
Access level: 1 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2634
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for missing enable signals that are preventing the closed-loop drive control from being
commissioned.
Bit field: Bit Signal name 1 signal 0 signal FP
00 OFF1 enable missing Yes No 7954
01 OFF2 enable missing Yes No -
02 OFF3 enable missing Yes No -
03 Operation enable missing Yes No -
04 DC braking enable missing Yes No -
08 Safety enable missing Yes No -
10 Ramp-function generator enable missing Yes No -
11 Ramp-function generator start missing Yes No -
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 481