p0771[0...2] CI: CU analog outputs signal source / CU AO s_s
Access level: 2 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2261
Min:
-
Max:
-
Factory setting:
[0] 21[0]
[1] 27[0]
[2] 0
Description: Sets the signal source for the analog outputs.
Index: [0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Note
AO: Analog Output
X202: IO module terminal
r0772[0...2] CU analog outputs output value currently referred / CU AO outp act ref
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Displays the actual referred output value of the analog outputs.
Index: [0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Note
AO: Analog Output
X202: IO module terminal
p0773[0...2] CU analog outputs smoothing time constant / CU AO T_smooth
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
0.0 [ms]
Max:
1000.0 [ms]
Factory setting:
0.0 [ms]
Description: Sets the smoothing time constant of the 1st order lowpass filter for the analog outputs.
Index: [0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Note
AO: Analog Output
X202: IO module terminal
Parameters
7.2 Parameter list
SINAMICS G120X converter
572 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC