4.2.6 Default setting of the interfaces (macros)
Overview
The function of most of the converter terminals can be set.
In order to avoid having to successively change terminal for terminal, multiple terminals can be
set jointly for quick commissioning. Parameter p0015 for quick commissioning initiates a macro
that adopts the setting of the terminals.
Table 4-9 Overview of default settings, Part 1/2
Default setting (macro)
Terminal 41 42 43 44 45 46
1)
47
AI 0 Setpoint Setpoint Setpoint Setpoint Setpoint Setpoint local -
AI 1 - PID actual
value
PID actual
value
PID actual
value
- Setpoint re‐
mote
PID actual
value
AO 0 Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
AO 1
2)
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
DI 0 ON/OFF2 ON/OFF2 ON/OFF2 ON/OFF2 ON/OFF2 ON/OFF2 lo‐
cal
ON/OFF2
DI 1 - - Service pump
1
Service pump
1
Fixed set‐
point 1
ON/OFF2 re‐
mote
-
DI 2 - - Service pump
2
Service pump
2
Fixed set‐
point 2
- -
DI 3 - - - Service pump
3
Fixed set‐
point 3
- -
DI 4 - manual ↔ au‐
to
manual ↔ au‐
to
manual ↔ au‐
to
- local remote -
DI 5 Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
DO 0 Fault Fault Fault Fault Fault Fault Fault
DO 1 Operation Operation Operation Pump 1 Operation Operation Operation
DO 2
2)
Ready for op‐
eration
Ready for op‐
eration
Pump 1 Pump 2 Ready for op‐
eration
Ready for op‐
eration
Ready for op‐
eration
DO 3
2)
Alarm Alarm Pump 2 Pump 3 Alarm Alarm Alarm
Fieldbus - - - - - - -
1)
For converters with USS fieldbus interfaces
2)
With I/O Extension Module
Wiring
4.2 Control interfaces
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 107