09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Dependency: See also: p2099
p2098[0...1] Inverter connector-binector converter binector output / Con/bin outp inv
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2468, 9360
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0000 bin
Description: Setting to invert the individual binector outputs of the connector-binector converter.
Using p2098[0], the signals of connector input p2099[0] are influenced.
Using p2098[1], the signals of connector input p2099[1] are influenced.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 Inverted Not inverted -
01 Bit 1 Inverted Not inverted -
02 Bit 2 Inverted Not inverted -
03 Bit 3 Inverted Not inverted -
04 Bit 4 Inverted Not inverted -
05 Bit 5 Inverted Not inverted -
06 Bit 6 Inverted Not inverted -
07 Bit 7 Inverted Not inverted -
08 Bit 8 Inverted Not inverted -
09 Bit 9 Inverted Not inverted -
10 Bit 10 Inverted Not inverted -
11 Bit 11 Inverted Not inverted -
12 Bit 12 Inverted Not inverted -
13 Bit 13 Inverted Not inverted -
14 Bit 14 Inverted Not inverted -
15 Bit 15 Inverted Not inverted -
Dependency: See also: r2094, r2095, p2099
p2099[0...1] CI: Connector-binector converter signal source / Con/bin s_s
Access level: 3 Calculated: - Data type: Unsigned32 /
Integer16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2468, 9360
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on
(interconnection).
Dependency: See also: r2094, r2095
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 763