p2320 Technology controller Tn adaptation lower starting point / Tn adapt lower pt
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7959
Min:
0.00 [%]
Max:
400.00 [%]
Factory setting:
0.00 [%]
Description: Sets the lower activation point for the adaptation of integral time Tn for the technology controller.
Dependency: See also: p2317, p2318, p2319, p2321, r2322
CAUTION
The upper starting point must be set higher than the lower starting point (p2321 > p2320).
Note
Tn adaptation is activated with p2252.8 = 1.
p2321 Technology controller Tn adaptation upper starting point / Tn adapt upper pt
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7959
Min:
0.00 [%]
Max:
400.00 [%]
Factory setting:
100.00 [%]
Description: Sets the upper activation point for the adaptation of integral time Tn for the technology controller.
Dependency: See also: p2317, p2318, p2319, p2320, r2322
CAUTION
The upper starting point must be set higher than the lower starting point (p2321 > p2320).
Note
Tn adaptation is activated with p2252.8 = 1.
r2322 CO: Technology controller Tn adaptation output / Tn adapt output
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7959
Min:
- [s]
Max:
- [s]
Factory setting:
- [s]
Description: Display and connector output for the output signal of the adaption of integral time Tn for the technology controller.
Dependency: See also: p2252, p2317, p2318, p2319, p2320, p2321
Note
Tn adaptation is activated with p2252.8 = 1.
p2339 Techn. controller threshold value f. I comp. hold for skip speed / Tec_ctrl thr_skip
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: 9_1 Unit selection: p0595 Function diagram: -
Min:
0.00 [%]
Max:
200.00 [%]
Factory setting:
2.00 [%]
Description: Sets the threshold value for the system deviation of the technology controller, which controls holding the controller
integral component in the range of the skip speeds of the ramp-function generator.
Recommendation: To avoid speed setpoint steps in the range of the skip speeds, we recommend setting p2252 bit 4 = 1 (ramp-function
generator bypass deactivated).
Parameters
7.2 Parameter list
SINAMICS G120X converter
812 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC