Siemens SINAMICS G120X - BI: Motorized Potentiometer Lower Setpoint; Mop Lower

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1035[0...n] BI: Motorized potentiometer setpoint raise / Mop raise
G120X_USS Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2505, 3020
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to continually increase the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-up time (p1047) and the duration of the signal that is
present (BI: p1035).
Dependency: See also: p1036
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1036[0...n] BI: Motorized potentiometer lower setpoint / Mop lower
G120X_DP,
G120X_PN
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2505, 3020
Min:
-
Max:
-
Factory setting:
[0] 2090.14
[1] 0
[2] 0
[3] 0
Description: Sets the signal source to continuously lower the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-down time (p1048) and the duration of the signal that is
present (BI: p1036).
Dependency: See also: p1035
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1036[0...n] BI: Motorized potentiometer lower setpoint / Mop lower
G120X_USS Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2505, 3020
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to continuously lower the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-down time (p1048) and the duration of the signal that is
present (BI: p1036).
Dependency: See also: p1035
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Parameters
7.2 Parameter list
SINAMICS G120X converter
616 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC