A01098 RTC: Date and time setting required
Reaction: NONE
Acknowledge: NONE
Cause: The power supply for the Control Unit was interrupted for an extended period. The date and time displayed on the real-time
clock are no longer accurate.
Note:
This alarm is only output when p8405 = 1 (factory setting).
See also: p8405 (Activate/deactivate RTC alarm A01098)
Remedy: Set the date and time on the real-time clock.
Note:
RTC: Real-time clock
See also: p8400, p8401
N01101 (A) CU: memory card not available
Reaction: NONE
Acknowledge: NONE
Cause: The memory card is not available for the drive.
Remedy: Insert a memory card.
If Starter is not active, interrupt the USB connection to the PC
F01105 (A) CU: Insufficient memory
Reaction: OFF1
Acknowledge: POWER ON
Cause: Too many data sets are configured on this Control Unit.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - reduce the number of data sets.
F01107 Save to memory card unsuccessful
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: A data save to the memory card was not able to be successfully carried out.
- Memory card defective
- insufficient space on memory card.
Fault value (r0949, interpret decimal):
1: The file on the RAM was not able to be opened.
2: The file on the RAM was not able to be read.
3: A new directory could not be created on the memory card.
4: A new file could not be created on the memory card.
5: A new file could not be written on the memory card.
Remedy: - try to save again.
- replace the memory card or Control Unit.
F01112 CU: Power unit not permissible
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The connected power unit cannot be used together with this Control Unit.
Fault value (r0949, interpret decimal):
1: Power unit is not supported (e.g. PM340).
Remedy: Replace the power unit that is not permissible by a component that is permissible.