9.3 Identification & maintenance data (I&M)
I&M data
The converter supports the following identification and maintenance (I&M) data.
I&M
data
Format Explanation Associated pa‐
rameters
Example for the
content
I&M0 u8[64] PROFIBUS
u8[54] PROFINET
Converter-specific data, read only - See below
I&M1 Visible String [32] Plant/system identifier p8806[0 … 31] "ak12-
ne.bo2=fu1"
Visible String [22] Location code p8806[32 53] "sc2+or45"
I&M2 Visible String [16] Date p8807[0 … 15] "2013-01-21
16:15"
I&M3 Visible String [54] Any comment p8808[0 … 53] -
I&M4 Octet String[54] Check signature to track changes
for Safety Integrated.
This value can be changed by the
user.
The test signature is reset to the
value generated by the machine if
p8805 = 0 is used.
p8809[0 … 53] Values of
r9781[0] and
r9782[0]
When requested, the converter transfers its I&M data to a higher-level control or to a PC/PG
with installed STEP 7 or TIA Portal.
I&M0
Designation Format Example for the
content
Valid for PRO‐
FINET
Valid for PRO‐
FIBUS
Manufacturer-specific u8[10] 00 … 00 hex ---
MANUFACTURER_ID u16 42d hex (=Sie‐
mens)
ORDER_ID Visible String
[20]
"6SL3246-0BA22-
1FA0"
SERIAL_NUMBER Visible String
[16]
"T-R32015957"
HARDWARE_REVISION u16 0001 hex
SOFTWARE_REVISION char, u8[3] "V" 04.70.19
REVISION_COUNTER u16 0000 hex
PROFILE_ID u16 3A00 hex
PROFILE_SPECIFIC_TYPE u16 0000 hex
IM_VERSION u8[2] 01.02
IM_SUPPORTED bit[16] 001E hex
Warnings, faults and system messages
9.3 Identification & maintenance data (I&M)
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 963