p3884 CI: ESM setpoint technology controller / ESM setp tech_ctrl
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7033
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the setpoint for p3881 = 4 (technology controller) in the essential service mode (ESM).
Dependency: See also: p3881
Note
ESM: Essential Service Mode
For p3884 = 0:
The technology controller uses the setpoint from p2253.
r3887[0...1] ESM number of activations/faults / ESM act/fault qty
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7033
Min:
-
Max:
-
Factory setting:
-
Description: Displays the number of activations and faults that have occurred for the essential service mode (ESM).
Index: [0] = Activation of the essential service mode
[1] = Faults during the essential service mode
Dependency: See also: p3888
Note
ESM: Essential Service Mode
p3888 ESM reset number of activations/faults / ESM act/F qty r
Access level: 4 Calculated: - Data type: Unsigned8
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7033
Min:
0
Max:
1
Factory setting:
0
Description: Setting to reset the number of activations and faults that have occurred for the essential service mode (ESM).
1: counter reset active (r3887[0, 1])
0: inactive
Dependency: See also: r3887
Note
ESM: Essential Service Mode
The parameter is automatically reset to zero after the counter has been reset.
r3889.0...10 CO/BO: ESM status word / ESM ZSW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7033
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the status word of the essential service mode (ESM).
Bit field: Bit Signal name 1 signal 0 signal FP
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 845