Note
Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here. In a long
list, index 99 contains the parameter number at which position the list continues.
This list consists solely of the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be read
from a higher-level control system (e.g. PROFIBUS master).
r0999[0...99] List of modified parameters 10 / List chang par 10
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays those parameters with a value other than the factory setting for this drive.
Dependency: See also: r0990, r0991
Note
Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here.
This list consists solely of the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be read
from a higher-level control system (e.g. PROFIBUS master).
p1000[0...n] Speed setpoint selection / n_set sel
G120X_DP,
G120X_PN
Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
200
Factory setting:
6
Description: Sets the source for the speed setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value: 0: No main setpoint
1: Motorized potentiometer
2: Analog setpoint
3: Fixed speed setpoint
6: Fieldbus
7: Analog setpoint 2
10: Motor potentiometer + no main setpoint
11: Motor potentiometer + motor potentiometer
12: Motor potentiometer + analog setpoint
13: Motor potentiometer + fixed speed setpoint
16: Motor potentiometer + fieldbus
17: Motor potentiometer + analog setpoint 2
Parameters
7.2 Parameter list
SINAMICS G120X converter
606 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC