p1829 Compensation valve lockout time phase V / Comp t_lock ph V
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 4 Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [µs]
Max:
7.80 [µs]
Factory setting:
0.00 [µs]
Description: Sets the valve lockout time to compensate for phase V.
p1830 Compensation valve lockout time phase W / Comp t_lock ph W
Access level: 4 Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [µs]
Max:
3.99 [µs]
Factory setting:
0.00 [µs]
Description: Sets the valve lockout time to compensate for phase W.
p1830 Compensation valve lockout time phase W / Comp t_lock ph W
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 4 Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [µs]
Max:
7.80 [µs]
Factory setting:
0.00 [µs]
Description: Sets the valve lockout time to compensate for phase W.
p1832 Dead time compensation current level / t_dead_comp I_lev
Access level: 4 Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.0 [Arms]
Max:
10000.0 [Arms]
Factory setting:
0.0 [Arms]
Description: Sets the current level for the dead time compensation.
Above the current level, the dead time - resulting from the converter switching delays - is compensated by a previously
calculated constant value. If the relevant phase current setpoint falls below the absolute value defined by p1832, the
corrective value for this phase is continuously reduced.
Dependency: The factory setting of p1832 is automatically set to 0.02 * rated drive converter current (r0207).
r1838.0...15 CO/BO: Gating unit status word 1 / Gating unit ZSW1
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for status word 1 of the power unit.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fault time-critical ON OFF -
01 Gating unit mode bit 0 ON OFF -
02 Pulse enable ON OFF -
03 Switch-off signal path STO_B Inactive Active -
04 Switch-off signal path STO_A Inactive Active -
Parameters
7.2 Parameter list