4.1.4.1 Connection overview
Note
Available options
For information about available options, see Chapter "Optional components (Page 32)".
&RQYHUWHU0RWRUVLGHRSWLRQ
/LQHVLGHRSWLRQ
9ROWDJH3HDN/LPLWHU
8
9
:
3(3(
:
9
8/
/
/
3(
:
9
8
/
/
/
3(
/
/
/
3(3(
/
/
/
'&16
'&36
3(:
9
8
)5
Figure 4-5 Connecting converters FSA … FSG and their optional components
Converter Line side option
1)
Motor side option
2)
Line harmonics filter Line filter Output reactor Sine-wave filter dv/dt filter + VPL
400 V
FSA ... FSC √
3)
√ -- -- --
FSD...FSG √ √ √ √ √
690 V
FSD ... FSG -- √ √ -- √
1)
If you choose to use line harmonics filter and line filter simultaneously, the order of connection should be: Line -> Line
harmonics filter -> Line filter -> Converter.
2)
If you choose to use the motor side option, it is enough to use only one of the options.
3)
Line harmonics filter is not provided for 400 V converters FSA.
Wiring
4.1 Line supply and motor
SINAMICS G120X converter
88 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC