p0779[0...2] CU analog outputs characteristic value x2 / CU AO char x2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
-1000.00 [%]
Max:
1000.00 [%]
Factory setting:
100.00 [%]
Description: Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Dependency: See also: p0776
NOTICE
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note
The parameters for the characteristic do not have a limiting effect.
X202: IO module terminal
p0780[0...2] CU analog outputs characteristic value y2 / CU AO char y2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
-20.000 [V]
Max:
20.000 [V]
Factory setting:
20.000 [V]
Description: Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the
characteristic.
Index: [0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Dependency: The unit of this parameter (V or mA) depends on the analog output type.
See also: p0776
NOTICE
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note
The parameters for the characteristic do not have a limiting effect.
X202: IO module terminal
p0782[0...2] BI: CU analog outputs invert signal source / CU AO inv s_s
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to invert the analog output signals.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 575