Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
r8413.0...1 BO: RTC DTC1 output / RTC DTC1 output
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Display and binector output for the output of time switch 1 (DTC1).
Where a weekday is deactivated, the following applies (p8410):
- the binector output for this timer is inactive (r8413.0 = 0).
Where a weekday is activated, the following applies (p8410):
- the ON/OFF time setting (p8411, p8412) for this timer has an instant effect on the binector output (r8413).
Bit field: Bit Signal name 1 signal 0 signal FP
00 Timer on Yes No -
01 Timer ON negated No Yes -
Dependency: See also: p8409, p8410, p8411, p8412
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8420[0...6] RTC DTC2 weekday of activation / RTC DTC2 day act
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description: Sets the weekday on which timer 2 is activated (DTC2).
The switch-on/off time is set in p8421/p8422 and the result displayed via binector output r8423.
Value: 0: Weekday deactivated
1: Weekday activated
Index: [0] = Monday
[1] = Tuesday
[2] = Wednesday
[3] = Thursday
[4] = Friday
[5] = Saturday
[6] = Sunday
Dependency: See also: p8409, p8421, p8422, r8423
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 871