p2016[0...3] CI: Comm IF USS PZD send word / Comm USS send word
Access level: 3 Calculated: - Data type: Unsigned32 /
Integer16
Can be changed: T, U Scaling: 4000H Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Selects the PZD (actual values) to be sent via the commissioning interface USS.
The actual values are displayed on an intelligent operator panel (IOP).
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
r2019[0...7] Comm IF error statistics / Comm err
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the receive errors at the commissioning interface (USS, RS232).
Index: [0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
p2020 Field bus interface baud rate / Field bus baud
G120X_USS Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9310
Min:
4
Max:
13
Factory setting:
8
Description: Sets the baud rate for the field bus interface (RS485).
Value: 4: 2400 baud
5: 4800 baud
6: 9600 baud
7: 19200 baud
8: 38400 baud
9: 57600 baud
10: 76800 baud
11: 93750 baud
12: 115200 baud
13: 187500 baud
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 735