EasyManua.ls Logo

Siemens SINAMICS G120X - CO: Temperature Sensor Exciting Current Output; Tempsen I_Out; CO: Temperature Sensor Resistance Value; Tempsen R; Profidrive Reference Speed Reference Frequency; PD N_Ref F_Ref; Temperature Sensor Exiting Current Set; Tempsen I_Exit

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
r29706 CO: Temperature sensor exciting current output / TempSen I_out
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Current output to temperature sensor in percent of 20mA.
Note
This CO parameter may connect to the analog output source set(e.g. p771[x]), which is the AO channel of sensor
connected.
r29707 CO: Temperature sensor resistance value / TempSen R
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
- [ohm]
Max:
- [ohm]
Factory setting:
- [ohm]
Description: Display the actual resistance value of the temperature sensor.
p29708 Temperature sensor exiting current set / TempSen I_exit
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [%]
Max:
100.00 [%]
Factory setting:
50.00 [%]
Description: Sets the exciting current of temperature sensor.
p60000 PROFIdrive reference speed reference frequency / PD n_ref f_ref
G120X_DP,
G120X_PN
Access level: 2 Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
6.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
1500.00 [rpm]
Description: Sets the reference quantity for speed and frequency.
All speeds or frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
The following applies: reference frequency (in Hz) = reference speed (in ((rpm) / 60) x pole pair number)
Dependency: See also: p2000
NOTICE
When the reference speed / reference frequency is changed, short-term communication interruptions may occur.
Parameters
7.2 Parameter list
SINAMICS G120X converter
934 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC

Table of Contents

Other manuals for Siemens SINAMICS G120X