Description: Sets the signal source for the speed/velocity limit of the negative direction.
p1091[0...n] Skip speed 1 / n_skip 1
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3050
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description: Sets skip speed 1.
Dependency: See also: p1092, p1093, p1094, p1101
NOTICE
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Note
The skip (suppression) speeds can be used to prevent the effects of mechanical resonance.
p1092[0...n] Skip speed 2 / n_skip 2
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3050
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description: Sets skip speed 2.
Dependency: See also: p1091, p1093, p1094, p1101
NOTICE
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
p1093[0...n] Skip speed 3 / n_skip 3
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3050
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description: Sets skip speed 3.
Dependency: See also: p1091, p1092, p1094, p1101
NOTICE
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
p1094[0...n] Skip speed 4 / n_skip 4
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3050
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description: Sets skip speed 4.
Dependency: See also: p1091, p1092, p1093, p1101
NOTICE
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Parameters
7.2 Parameter list
SINAMICS G120X converter
628 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC