Note
DO: Digital Output
X204: IO module terminal
Relay output: NO = normally open
p0734 BI: CU signal source for terminal DO 4 / CU s_s DO 4
G120X_USS Access level: 2 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for terminal DO 4(NO: X204. 93)..
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
DO: Digital Output
X204: IO module terminal
Relay output: NO = normally open
p0735 BI: CU signal source for terminal DO 5 / CU s_s DO 5
Access level: 2 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for terminal DO 5 (NO: x204. 91).
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
DO: Digital Output
X204: IO module terminal
Relay output: NO = normally open
r0747 CU digital outputs status / CU DO status
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2130, 2131,
2132, 2133
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status of digital outputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (NO: X134. 19 / NC: X134. 18) High Low -
01 DO 1 (NO: X134. 24 / NC: X134. 23) High Low -
02 DO 2 (NO: X204. 98 / NC: X204. 99) High Low -
03 DO 3 (NO: X204. 95 / NC: X204. 96) High Low -
04 DO 4 (NO: X204. 93) High Low -
05 DO 5 (NO: X204. 91) High Low -
Parameters
7.2 Parameter list