Description: Displays the control word for the two wire control/three wire control.
The control signals are dependent on the wire control set in p0015 and the signal states at the digital inputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON Yes No -
01 Reversing Yes No -
02 ON inverted Yes No -
03 Reversing inverted Yes No -
Dependency: See also: p0015, p3330, p3331, p3332, p3334
p3334 2/3 wire control selection / 2/3 wire select
Access level: 4 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2272, 2273
Min:
0
Max:
4
Factory setting:
0
Description: Sets the two wire control/three wire control.
Value: 0: No wire control
1: Two wire control clockwise/counterclockwise 1
2: Two wire control clockwise/counterclockwise 2
3: Three wire control enable clockwise/counterclockwise
4: Three wire control enable ON/reversing
Dependency: See also: p0015, p3330, p3331, p3332, r3333
Note
This value depends on the wire control set in p0015.
p3340[0...n] BI: Limit switch start / Lim switch start
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the start of motion dependent on the sign of the setpoint.
Dependency: See also: p3342, p3343, r3344
See also: A07352
p3342[0...n] BI: Limit switch plus / Lim switch plus
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source for the limit switch plus.
BI: p3342 = 1-signal:
Limit switch is inactive.
BI: p3342 = 0 signal:
Limit switch is active.
Dependency: See also: p3340, p3343, r3344
Parameters
7.2 Parameter list
SINAMICS G120X converter
838 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC