r0752[0...3] CO: CU analog inputs input voltage/current actual / CU AI U/I_inp act
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p0514 Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568,
9576
Min:
-
Max:
-
Factory setting:
-
Description: Displays the actual input voltage in V when set as voltage input.
Displays the actual input current in mA when set as current input and with the load resistor switched in.
Displays the actual temperature in °C when set as temperature sensor and the voltage divider is switched in.
Index: [0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Dependency: The type of analog input AIx (voltage, current or temperature input) is set using p0756.
See also: p0756
Note
AI: Analog Input
X202: IO module terminal
p0753[0...3] CU analog inputs smoothing time constant / CU AI T_smooth
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568,
9576
Min:
0.0 [ms]
Max:
1000.0 [ms]
Factory setting:
0.0 [ms]
Description: Sets the smoothing time constant of the 1st order lowpass filter for the analog inputs.
Index: [0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Note
AI: Analog Input
X202: IO module terminal
r0755[0...3] CO: CU analog inputs actual value in percent / CU AI value in %
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568,
9576
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Displays the currently referred input value of the analog inputs.
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index: [0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Parameters
7.2 Parameter list
SINAMICS G120X converter
566 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC