Function description
Table 4-1 Converter operated on a TN system
Converter Line supply with grounded neutral Line supply with grounded phase conduc‐
tor and a voltage ≤ 600 V phase to phase
Frame size A B C D E F G H J A B C D E F G H J
Without line
filter
✓ ✓ ✓ ✓ ✓ ✓ ○ ○ ○ ✓ ✓ ✓ ✓ ✓ ✓ ○ ○ ○
Integrated
line filter C2
✓ ✓ ✓ ✓ ✓ ✓ ✓ ○ ○ - - - - - - ✓
1)
○ ○
Integrated
line filter C3
○ ○ ○ ○ ○ ✓ ✓ ✓ ✓ ○ ○ ○ ○ ○ - ✓
1)
✓
1)
✓
1)
✓ = Operation permissible
✓
1)
Operation permissible once grounding screw has been removed
If the grounding screw has been removed, the converter no longer fulfills the requirements of class C3.
- Operation not permissible
○ Converter not available
More information on removing the grounding connection in the converter:
Removing functional grounding of the converter (Page 78)