r5600 Pe energy-saving mode ID / Pe mode ID
G120X_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2381, 2382
Min:
0
Max:
255
Factory setting:
-
Description: Displays the PROFIenergy mode ID of the effective energy-saving mode.
Value: 0: POWER OFF
2: Energy-saving mode 2
240: Operation
255: Ready
Note
Pe: PROFIenergy profiles
p5602[0...1] Pe energy-saving mode pause time minimal / Pe mod t_pause min
G120X_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2381
Min:
300000 [ms]
Max:
4294967295 [ms]
Factory setting:
[0] 300000 [ms]
[1] 480000 [ms]
Description: Sets the minimum possible pause time for the energy-saving mode.
The value is the sum of the following times:
- Energy-saving mode transition time
- Operating state transition time regular
- Energy-saving mode, time of minimum stay
Index: [0] = Reserved
[1] = Mode 2
Note
It is not permissible that the value is less than the sum of the "energy-saving mode transition time" and the "operating
state transition time" (system properties).
Pe: PROFIenergy profiles
p5606[0...1] Pe energy-saving mode time of maximum stay / Pe t_max_stay
G120X_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2381
Min:
0 [ms]
Max:
4294967295 [ms]
Factory setting:
4294967295 [ms]
Description: Sets the time of maximum stay for the energy-saving mode.
Index: [0] = Reserved
[1] = Mode 2
Note
Pe: PROFIenergy profiles
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 857