0: DI0
1: DI1
2: DI2
3: DI3
4: DI4
5: DI5
Note
On variants with PN/DP interface, ON/OFF2 is disabled as default(p29650=-1), when enabled(p29650>=0), the
configuration of p840 and p844 will not be updated internally. ON/OFF2 is only effective if both are configured as r29659
bit0 and bit1 respectively.
p29651[0...n] BI: ON/OFF1 (OFF1) / ON/OFF1 (OFF1)
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the command "ON/OFF1 (OFF1)".
p29652[0...n] BI: ON/OFF2 (OFF2) / ON/OFF2 (OFF2)
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the command "ON/OFF2 (OFF2)".
r29659.0...1 CO/BO: Command word / Cmd word
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Command status is for ON/OFF1, OFF2 which can connect to p0840, p0844.
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Active Inactive -
01 coast-down(OFF2) signal source Active Inactive -
p29700[0...n] Temperature sensor type / TempSen type
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
3
Factory setting:
0
Description: Sets the sensor type for temperature measurement.
This means that the temperature sensor type is selected and the evaluation is switched in.
Value: 0: Evaluation disabled
1: 1 x PT100
2: 2 x PT100
Parameters
7.2 Parameter list
SINAMICS G120X converter
932 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC