Article number
Converter frame
size
Rated power (kW) Sine-wave filter
400 V converters
FSD 18.5 … 22 6SL3202-0AE24-6SA0
30 6SL3202-0AE26-2SA0
37 6SL3202-0AE28-8SA0
FSE 45
55 6SL3202-0AE31-5SA0
FSF 75
90 6SL3202-0AE31-8SA0
110 … 132 6SL3000-2CE32-3AA0
FSG
1)
160 6SL3000-2CE32-8AA0
200 6SL3000-2CE33-3AA0
250 6SL3000-2CE34-1AA0
1)
For converter FSG with sine-wave filter, operation is only permissible in the vector control mode. It is
not permissible for U/f mode to be used.
2.6.6 dv/dt filter plus VPL
Note
dv/dt filters plus VPL are available as optional components for converters FSD to FSJ only.
A combination of dv/dt filter and a voltage peak limiter (VPL) - dv/dt filter plus VPL - are available
to suppress voltage peaks and enable longer motor cables to be connected.
Maximum permissible motor cable length (Page 82)
When using the dv/dt filter plus VPL, observe the following restrictions:
● The maximum output frequency is 150 Hz.
● The maximum pulse frequency is 4 kHz.
NOTICE
Damage to the dv/dt filter plus VPL if it is not activated during commissioning
The dv/dt filter plus VPL may be damaged if it is not activated during commissioning.
● Activate the dv/dt filter plus VPL during commissioning via parameter p0230.
● Activate the dv/dt filter plus VPL during commissioning according to the electric
specifications.
Description
2.6 Optional components
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 39