05 Use voltage measured values for flying restart Yes No -
07 Voltage calibration when switching on Yes No -
08 Voltage monitoring when switching on Yes No -
09 Voltage monitoring cyclic Yes No -
Note
The motor data identification must be executed when using the voltage measurement.
p0251[0...n] Operating hours counter power unit fan / PU fan t_oper
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dynamic index: PDS, p0120
Unit group: - Unit selection: - Function diagram: -
Min:
0 [h]
Max:
4294967295 [h]
Factory setting:
0 [h]
Description: Displays the power unit fan operating hours.
The number of hours operated can only be reset to 0 in this parameter (e.g. after a fan has been replaced).
Dependency: See also: p0252
See also: A30042
Note
For liquid-cooled chassis power units, the operating hours of the inner fan are displayed in p0251 and not in p0254.
p0252 Maximum operating time power unit fan / PU fan t_oper max
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0 [h]
Max:
100000 [h]
Factory setting:
40000 [h]
Description: Sets the maximum operating time of the power unit fan.
The prealarm (warning) is output 500 hours before this set value.
The monitoring is deactivated with p0252 = 0.
Dependency: See also: p0251
See also: A30042
Note
For PM330 power units, the maximum operating time of the fan on the power unit is saved and displayed in p0252. The
"Restore factory setting" function or a project download does not influence p0252. Users can manually change the
maximum operating time of the fan. The modified value is also saved to the power unit.
p0254[0...n] Operating hours counter power unit fan inside the converter / PU inner fan t_op
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dynamic index: PDS, p0120
Unit group: - Unit selection: - Function diagram: -
Min:
0 [h]
Max:
4294967295 [h]
Factory setting:
0 [h]
Description: Displays the power unit fan operating hours of the internal fan in the power unit.
The number of hours operated can only be reset to 0 in this parameter (e.g. after a fan has been replaced).
Dependency: See also: A30042
Note
For liquid-cooled chassis power units, the operating hours of the inner fan are displayed in p0251 and not in p0254.
Parameters
7.2 Parameter list
SINAMICS G120X converter
508 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC