EasyManua.ls Logo

Siemens SINAMICS G120X - Low Frequency Performance

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.6 Low frequency performance
The converter can only be operated with reduced output current at low output frequencies.
NOTICE
Reduced converter service life as a result of overheating
Loading the converter with a high output current and at the same time with a low output
frequency can cause the current-conducting components in the converter to overheat.
Excessively high temperatures can damage the converter or reduce the converter service life.
Never operate the converter continuously with an output frequency = 0 Hz.
Only operate the converter in the permissible operating range.
&RQWLQXRXVRSHUDWLRQ
6SRUDGLFVKRUWWLPHGXW\6KRUWWLPHGXW\
2XWSXWIUHTXHQF\>+]@
3HUPLVVLEOH
RXWSXWFXUUHQW
>@
ืV
ืV
ืV















Continuous operation (green area in the figure)
Operating state that is permissible for the complete operating time.
Short-time duty (yellow area in the figure)
Operating state that is permissible for less than 2% of the total operating time.
Sporadic short-time duty (red area in the figure)
Operating state that is permissible for less than 0.1% of the total operating time.
Technical data
11.6 Low frequency performance
SINAMICS G120X converter
1098 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC

Table of Contents

Other manuals for Siemens SINAMICS G120X

Related product manuals