6.3.2.4 Analog inputs
Function description
,
8,
8,
S>@
$,
$,
U>@
&,S\\\\
S>@
$,
$,
U>@
&,S\\\\
S>@
$,
U>@
&,S\\\\
S>@
$,
*1'
U>@
&,S\\\\
˽
˽
7(03
7(03
1)
with I/O Extension Module
Define the analog input type
The parameter p0756[x] and the switch on the converter specify the analog input type.
Table 6-4 Default settings via parameter p0756
AI 0 Unipolar voltage input 0 V … +10 V p0756[0] = 0
Unipolar voltage input monitored +2 V … +10 V 1
Unipolar current input 0 mA … +20 mA 2
Unipolar current input monitored +4 mA … +20 mA 3
Bipolar voltage input (factory setting) ‑10 V … +10 V 4
AI 1 Unipolar voltage input 0 V … +10 V p0756[1] = 0
Unipolar voltage input monitored +2 V … +10 V 1
Unipolar current input 0 mA … +20 mA 2
Unipolar current input monitored +4 mA … +20 mA 3
Bipolar voltage input (factory setting) ‑10 V … +10 V 4
AI 2 Unipolar current input (factory setting) 0 mA … +20 mA p0756[2] = 2
Unipolar current input monitored +4 mA … +20 mA 3
LG-Ni1000 temperature sensor 6
Pt1000 temperature sensor 7
No sensor connected 8
DIN-Ni1000 temperature sensor (6180 ppm / K) 10
AI 3 LG-Ni1000 temperature sensor p0756[3] = 6
Pt1000 temperature sensor 7
No sensor connected (factory setting) 8
DIN-Ni1000 temperature sensor (6180 ppm / K) 10
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
196 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC