The switch that belongs to the analog input is located behind the front door of the
converter.
,8
$,
$,
The switch for AI 2 (temperature/current) is on the I/O Extension Module.
$,
7HPS,
Defining the function of an analog input
You define the analog input function by interconnecting a connector input of your choice with
parameter p0755. Parameter p0755 is assigned to the particular analog input via its index, e.g.
parameter p0755[0] is assigned to analog input 0.
Connector inputs are designated in the parameter list with the prefix "CI".
Example
$,
U>@>@
S
In order to enter the supplementary setpoint via analog input AI 0, you must interconnect AI 0
with the signal source for the supplementary setpoint.
Set p1075 = 755[0].
Parameters
Table 6-5 Frequently used connector inputs (CI) of the converter
Parameter Description Factory setting
p1070[C] CI: Main setpoint Dependent on the converter
p1075[C] CI: Supplementary setpoint 0
p2253[C] CI: Technology controller setpoint 1 0
p2264[C] CI: Technology controller actual value 0
You can find additional connector inputs in the parameter list.
Parameter list (Page 470)
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 197