To meet the requirements of conducted emissions in accordance with C1, you must observe
the maximum motor cable length and also install ferrite sleeves on the FSD FSF converter.
Converter frame
size
400 V
Ferrite sleeve Installation
FSD Schaffner RU41572-1 1 ferrite sleeve per line terminal L1, L2 and L3
FSE Schaffner VAC
W517-02
1 ferrite sleeve per motor terminal U2, V2 and W2
FSF Schaffner RU41572-2 2 ferrite sleeves per line terminal L1, L2 and L3 and
2 ferrite sleeves per motor terminal U2, V2 and W2
Install the ferrite sleeves as closely as possible to the converter terminals on the connecting
cables.
Figure 4-4 Ferrite sleeves on the connecting cables
Wiring
4.1 Line supply and motor
SINAMICS G120X converter
84 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC