Parameters
Number Name Factory setting
p0347[M] Motor de-excitation time 0 s
p1260 Bypass configuration (factory setting: 0)
0: Bypass is deactivated
3: Bypass without synchronization
0
r1261.0…11 Bypass control/status word -
.00 1 signal: Close converter - motor contactor
.01 1 signal: Close line - motor contactor
p1262[D] Bypass dead time 1 s
p1263 Debypass (revert to drive) delay time 1 s
p1264 Bypass delay time 1 s
p1265 Bypass speed threshold 1480 rpm
p1266 BI: Bypass control command 0
p1267 Bypass changeover source configuration 0000 bin
p1269[0…1] BI: Bypass switch feedback signal [0] 1261.0
[1] 1261.1
[0] 1 signal: Converter - motor contactor is closed
[1] 1 signal: Line - motor contactor is closed
p1274[0...1] Bypass switch monitoring time 1000 ms
More information is provided in the parameter list.
Parameters (Page 467)
More information
Interaction with other functions:
Essential service mode
The activated "Essential service mode" function influences the "Bypass" function.
Essential service mode (Page 429)
Converter control
For operation of the motor on the line supply, the converter no longer responds to the OFF1
command, but rather only to OFF2 and OFF3.
Temperature monitoring for the motor
The converter evaluates the temperature sensor in the motor, also for line operation of the
motor.
Motor protection with temperature sensor (Page 409)
Disconnecting the converter from the line supply
If for line operation of the motor, you disconnect the converter from the line supply, the
converter opens the K2 contactor and the motor coasts down.
To operate the motor on the line supply also for deactivated converter, the higher-level
control must supply the signal for the K2 line contactor.
Advanced commissioning
6.10 Energy saving
SINAMICS G120X converter
444 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC