Note
DO: Digital Output
X204: IO module terminal
Relay output: NO = normally open, NC = normally closed
Inversion using p0748 has been taken into account.
p0748 CU invert digital outputs / CU DO inv
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2201, 2242
Min:
-
Max:
-
Factory setting:
0000 0000 bin
Description: Setting to invert the signals at the digital outputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (NO: X134. 19 / NC: X134. 18) Inverted Not inverted -
01 DO 1 (NO: X134. 24 / NC: X134. 23) Inverted Not inverted -
02 DO 2 (NO: X204. 98 / NC: X204. 99) Inverted Not inverted -
03 DO 3 (NO: X204. 95 / NC: X204. 96) Inverted Not inverted -
04 DO 4 (NO: X204. 93) Inverted Not inverted -
05 DO 5 (NO: X204. 91) Inverted Not inverted -
Note
DO: Digital Output
X204: IO module terminal
Relay output: NO = normally open, NC = normally closed
r0751.0...11 BO: CU analog inputs status word / CU AI status word
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2251, 2252
Min:
-
Max:
-
Factory setting:
-
Description: Display and binector output for the status of the analog inputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Analog input AI0 wire breakage Yes No -
01 Analog input AI1 wire breakage Yes No -
02 Analog input AI2 wire breakage Yes No -
03 Analog input AI3 wire breakage Yes No -
08 Analog input AI0 no wire breakage Yes No -
09 Analog input AI1 no wire breakage Yes No -
10 Analog input AI2 no wire breakage Yes No -
11 Analog input AI3 no wire breakage Yes No -
Note
AI: Analog Input
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 565