Remedy: Enter the clock cycle of an existing time slice with a cycle time >= 2 ms for up to 4 recording channels or >= 4 ms from 5
recording channels per trace.
The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02059 Trace: Time slice clock cycle for 2 x 8 recording channels not valid
Reaction: NONE
Acknowledge: NONE
Cause: The selected time slice clock cycle cannot be used for more than 4 recording channels.
See also: p4723 (Trace time slice cycle)
Remedy: Enter the clock cycle of an existing time slice with a cycle time >= 4 ms or reduce the number of recording channels to 4
per trace.
The existing time slices can be read out via p7901.
See also: p4702, r7901
A02060 Trace: Signal to be traced missing
Reaction: NONE
Acknowledge: NONE
Cause: - a signal to be traced was not specified.
- the specified signals are not valid.
See also: p4730, p4731, p4732, p4733
Remedy: - specify the signal to be traced.
- check whether the relevant signal can be traced.
A02061 Trace: Invalid signal
Reaction: NONE
Acknowledge: NONE
Cause: - the specified signal does not exist.
- the specified signal can no longer be traced (recorded).
See also: p4730, p4731, p4732, p4733
Remedy: - specify the signal to be traced.
- check whether the relevant signal can be traced.
A02062 Trace: Invalid trigger signal
Reaction: NONE
Acknowledge: NONE
Cause: - a trigger signal was not specified.
- the specified signal does not exist.
- the specified signal is not a fixed-point signal.
- the specified signal cannot be used as a trigger signal for the trace.
See also: p4711 (Trace trigger signal)
Remedy: Specify a valid trigger signal.
A02063 Trace: Invalid data type
Reaction: NONE
Acknowledge: NONE
Cause: The specified data type to select a signal using a physical address is invalid.
See also: p4711, p4730, p4731, p4732, p4733
Remedy: Use a valid data type.
Warnings, faults and system messages
9.6 List of fault codes and alarm codes
SINAMICS G120X converter
990 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC