No. Service Type Name Value/explanation
6 get UINT32 Serial number bits 0 … 19: consecutive number;
bits 20 … 23: Production identifier
bits 24 … 27: Month of manufacture (0 = Jan, B =
Dec)
Bits 28 … 31: Year of manufacture (0 = 2002)
7 get Short
String
Product name Max. length 32 bytes
Table 6-21 Explanation of No. 5 of the previous table
Byte Bit Name Description
1 0 Owned 0: Converter is not assigned to any master
1: Converter is assigned to a master
1 Reserved
2 Configured 0: Ethernet/IP basic settings
1: Modified Ethernet/IP settings
For G120, always = 1
3 Reserved
4 … 7 Extended De‐
vice Status
0: Self-test or status not known
1: Firmware update active
2: At least one I/O connection with error
3: No I/O connections
4: Incorrect configuration in the ROM
5: Fatal fault
6: At least one I/O connection is active
7: All I/O connections in the quiescent state
8 … 15: Reserved
2 8 … 11 Not used
12 … 15 Reserved
Assembly Object, Instance Number: 4 hex
Supported services
Class ● Get Attribute single Instance ● Get Attribute single
● Set Attribute single
Table 6-22 Class Attribute
No. Service Type Name
1 get UINT16 Revision
2 get UINT16 Max Instance
3 get UINT16 Num of Instances
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
228 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC