r8935[0...5] PN MAC address / PN MAC addr
G120X_PN Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0000 hex
Max:
00FF hex
Factory setting:
-
Description: Displays the MAC address for the onboard PROFINET interface on the Control Unit.
r8939 PN DAP ID / PN DAP ID
G120X_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the PROFINET Device Access Point ID (DAP ID) for the onboard PROFINET interface.
The combination of device ID (r8909) and DAP ID uniquely identifies a PROFINET access point.
Note
List of the SINAMICS DAP IDs:
20007 hex: CBE20 V4.5
20008 hex: CBE20 V4.6
20107 hex: CU310-2 PN V4.5
20108 hex: CU310-2 PN V4.6
20307 hex: CU320-2 PN V4.5
20308 hex: CU320-2 PN V4.6
20407 hex: CU230P-2 PN /CU240x-2 PN V4.5
20408 hex: CU230P-2 PN /CU240x-2 PN /CU250S-2 PN /G110M PN V4.6
20507 hex: CU250D-2 PN V4.5
20508 hex: CU250D-2 PN V4.6
p8980 Ethernet/IP profile / Eth/IP profile
G120X_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2473
Min:
0
Max:
1
Factory setting:
0
Description: Sets the profile for Ethernet/IP.
Value: 0: SINAMICS
1: ODVA AC/DC
Note
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
ODVA: Open DeviceNet Vendor Association
p8981 Ethernet/IP ODVA STOP mode / Eth/IP ODVA STOP
G120X_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2473
Min:
0
Max:
1
Factory setting:
0
Description: Sets the STOP mode for the Ethernet/IP ODVA profile (p8980 = 1).