5.4.4 Selecting an application class
Application class Standard Drive Control Dynamic Drive Control
Properties
Typical settling time after a speed change:
100 ms … 200 ms
Typical settling time after a load surge: 500 ms
6SHHG
/RDG
0RWRU
WRUTXH
W
W
W
PV
Standard Drive Control is suitable for the
following requirements:
Motor power ratings < 45 kW
Ramp-up time 0 → rated speed (depending
on the motor power rating):
1 s (0.1 kW) … 10 s (45 kW)
Applications with steady load torque without
load surges
Standard Drive Control is insensitive with
respect to imprecise setting of the motor data
Typical settling time after a speed change:
< 100 ms
Typical settling time after a load surge: 200 ms
6SHHG
/RDG
0RWRU
WRUTXH
W
W
PV
Dynamic Drive Control controls and limits the
motor torque
Torque accuracy that can be achieved: ± 5% for
15% … 100% of the rated speed
We recommend Dynamic Drive Control for the
following applications:
Motor power ratings > 11 kW
For load surges of 10% … >100% of the
rated motor torque
Dynamic Drive Control is necessary for a ramp-
up time 0 rated speed (dependent on the rated
motor power): < 1 s (0.1 kW) < 10 s (132 kW).
Application ex‐
amples
Pumps, fans, and compressors with flow
characteristic
Pumps and compressors with displacement
machines
Motors that can
be operated
Induction motors Induction and synchronous motors
Max. output fre‐
quency
550 Hz 240 Hz
Torque control Without torque control Speed control with lower-level torque control
Commissioning
Unlike "Dynamic Drive Control," no speed
controller needs to be set
Compared with the "EXPERT" setting:
Simplified commissioning using predefined
motor data
Reduced number of parameters
Standard Drive Control is preset for converters
of frame size A … frame size C
Fewer parameters compared with the
"EXPERT" setting
Dynamic Drive Control is preset for converters
of frame size D … frame size J
Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
SINAMICS G120X converter
162 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC