CAUTION
If p1000 is selected as the main setpoint of the fieldbus, the following BICO interconnection is set automatically:
p2051[1] = r0063
p1001[0...n] CO: Fixed speed setpoint 1 / n_set_fixed 1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description: Setting and connector output for fixed speed setpoint 1.
Dependency: See also: p1020, p1021, p1022, p1023, r1024, r1197
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1002[0...n] CO: Fixed speed setpoint 2 / n_set_fixed 2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description: Setting and connector output for fixed speed setpoint 2.
Dependency: See also: p1020, p1021, p1022, p1023, r1024, r1197
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1003[0...n] CO: Fixed speed setpoint 3 / n_set_fixed 3
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description: Setting and connector output for fixed speed setpoint 3.
Dependency: See also: p1020, p1021, p1022, p1023, r1024, r1197
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1004[0...n] CO: Fixed speed setpoint 4 / n_set_fixed 4
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description: Setting and connector output for fixed speed setpoint 4.
Dependency: See also: p1020, p1021, p1022, p1023, r1024, r1197
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 609