Parameters
Number Name Factory setting
p0010 Drive commissioning parameter filter 1
p0230 Drive filter type, motor side 0
p0235 Number of motor reactors in series 1
p0350[M] Motor stator resistance, cold 0 Ω
p0352[M] Cable resistance 0 Ω
For additional information on parameters, please refer to the parameter list.
6.7.2 V/f control
6.7.2.1 U/f control
Overview
9IFKDUDFWHUL
VWLF
6OLSFRPSHQVD
WLRQ
9ROWDJHERRVW
6RIWVWDUW
QൺI
6SHHGVHWSRLQW
I
VHW
8
VHW
2XWSXWYROWDJH
2XWSXWIUHTXHQF\
&XUUHQWVHWSRLQW,
TBVHW
,
TBVHW

U
U
U
U
0
Q
8
I
1)
In the "Flux Current Control (FCC)" U/f version, the converter controls the motor current (starting
current) at low speeds.
Figure 6-67 Simplified function diagram of the U/f control
The U/f control is a speed feedforward control with the following properties:
The converter sets the output voltage on the basis of the U/f characteristic.
The output frequency is essentially calculated from the speed setpoint and the number of
pole pairs of the motor.
The slip compensation corrects the output frequency depending on the load and thus
increases the speed accuracy.
The omission of a control loop means that the U/f control is stable in all cases.
In applications with higher speed accuracy requirements, a load-dependent voltage boost
can be selected (flux current control, FCC)
For operation of the motor with U/f control, you must set at least the following subfunctions
appropriate for your application:
V/f characteristic
Voltage boost
Advanced commissioning
6.7 Motor control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 377