EasyManua.ls Logo

Siemens SINAMICS G120X - Compound Braking Current; Compound I_Brake; DC Quantity Controller Configuration; Rect_Ctrl Config

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
02 Forming completed Yes No -
03 Forming fault Yes No -
Dependency: See also: p3380, r3381
See also: F07390, A07391
Note
For bit 00 = 1:
The parameter for activation/duration has been set (p3380 > 0) - however, forming has still not been started (p0840 =
0 signal).
For bit 01 = 1:
The parameter for activation/duration has been set (p3380 > 0) - however, forming has still not been started (p0840 =
0/1 signal).
This status is displayed through alarm A07391.
The procedure can be interrupted via binector input p0840, p0844, p0848 (r3382.1 = 0) - and reactivated again using
p0840.
For bit 03 = 1:
Forming was not able to be successfully performed within the set duration.
This status is displayed using fault F07390.
p3855[0...n] DC quantity controller configuration / Rect_ctrl config
Access level: 3 Calculated:
CALC_MOD_LIM_REF
Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 6797, 6844,
6855
Min:
-
Max:
-
Factory setting:
0111 bin
Description: Sets the configuration for the DC quantity controller in the overmodulation range.
There is no DC quantity control for power units that can also be connected through 1 phase to the line supply (r0204.15
= 1).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DC quantity controller on Yes No -
01 Bandwidth increased Yes No -
02 7th harmonic reduced Yes No -
03 Filter active Yes No -
Dependency: The modulator mode p1802 must enable operation in the overmodulation range. In addition, the overmodulation limit
p1803 must be greater than 103 %.
Set the modulator mode p1802 = 10, if the DC quantity control is deactivated and overmodulation is to be prevented.
NOTICE
Motor identification must be carried out before activating the DC quantity control in the overmodulation range.
p3856[0...n] Compound braking current / Compound I_brake
G120X_DP
(Compound brake),
G120X_PN
(Compound brake),
G120X_USS
(Compound brake)
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [%]
Max:
250.00 [%]
Factory setting:
0.00 [%]
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 841

Table of Contents

Other manuals for Siemens SINAMICS G120X

Related product manuals