p29611[0...n] Pipe filling mode / PF mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description: Selects the mode for pipe filling.
Value: 0: The pipe is filled based on specified time
1: The pipe is filled based on the actual pressure feedback
p29612[0...n] Pipe filling speed / PF spd
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: -
Min:
-210000.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
900.00 [rpm]
Description: Sets the speed applied to the motor for the pipe filling.
p29613[0...n] Pipe filling time / PF time
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.50 [s]
Max:
10000.00 [s]
Factory setting:
50.00 [s]
Description: Sets the duration time for the pipe filling.
p29614[0...n] Pipe filling threshold / PF thresh
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Function diagram: -
Min:
0.00 [%]
Max:
100.00 [%]
Factory setting:
10.00 [%]
Description: Defines the threshold for stopping the pipe filling. The filling stops if the actual PID feedback reaches the threshold.
It's used when p29611=1.
p29615[0...n] Pipe filling monitoring time / PF mon time
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [s]
Max:
100.00 [s]
Factory setting:
0.00 [s]
Description: Monitors the duration time for actual pressure (r2272) >= the threshold (p29614). The pipe filling stops if the duration
time is reached.
Note
It is used when p29611 = 1.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 927